Hoppa till innehåll
Free shipping on orders over 3000 kr excl. VAT! Volume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%
Volume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%How to Know Your Original Gravity Without Waiting for the Wort to CoolA Few Drops of Milk Are Enough to Tell Whether the Calf Gets the Right StartThe True Sugar Content of Wort and the Freezing Point of Glycol Can Be Measured with the Same InstrumentWhy a standard Brix refractometer shows the wrong sugar content in wortWhy Many Salinity Meters Give Wrong Readings: Seawater Is More Than Sodium ChlorideBath concentration determined in seconds with two drops and the press of a buttonSame sample, different temperature, different result: how to get a Brix value you can trustSame sample, three readings: how to get a Brix value that doesn’t depend on who is lookingThree Seconds and One Number: Brix Measurement Without Interpreting a Boundary LineThe same refractometer checks the sugar content in juice and the concentration in coolantVolume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%How to Know Your Original Gravity Without Waiting for the Wort to CoolA Few Drops of Milk Are Enough to Tell Whether the Calf Gets the Right StartThe True Sugar Content of Wort and the Freezing Point of Glycol Can Be Measured with the Same InstrumentWhy a standard Brix refractometer shows the wrong sugar content in wortWhy Many Salinity Meters Give Wrong Readings: Seawater Is More Than Sodium ChlorideBath concentration determined in seconds with two drops and the press of a buttonSame sample, different temperature, different result: how to get a Brix value you can trustSame sample, three readings: how to get a Brix value that doesn’t depend on who is lookingThree Seconds and One Number: Brix Measurement Without Interpreting a Boundary LineThe same refractometer checks the sugar content in juice and the concentration in coolant

IRIS Inline Process Refractometer: When Brix measurement is mounted directly in the pipeline and reports 4-20 mA to the control system every second

Published July 11, 2026 at 07:11

An apple juice concentrate manufacturer runs its evaporators from 06:00 every morning. Fresh juice (12-14% Brix) is fed into the evaporator; finished concentrate at 65% Brix flows out. In between, the liquid is stored and concentrated for 4-8 hours depending on pressure and temperature. If the final Brix is 63%, the product is under spec and cannot be sold as ”concentrate”. If the final Brix is 68%, the product is over-concentrated, the taste changes negatively, and storage can cause crystallization problems.

Traditional solution: an operator takes a sample from the outflow every hour, brings it to the lab, measures Brix on a handheld refractometer, and communicates the result back to the control system. This workflow has several problems:

  • An hour’s delay between sample and action. If there’s a problem, a lot of product ends up out of spec before anyone intervenes.
  • Sample handling is a source of error (contamination, temperature drift during transport).
  • Labor time — the operator’s handling time is expensive.
  • No continuous data for statistical process control (SPC) or rule-based management.

The solution: an INLINE process refractometer that measures Brix directly in the pipe stream continuously and reports to the control system in real time. IRIS is one such device.

Handheld vs. inline: the fundamental architectural difference

Handheld refractometers (like the Palm Abbe or ATAGO SugarMaster) are stand-alone instruments. The operator takes a sample, places it on the instrument, reads the value, and records it. Their design parameters:

  • Battery-powered or USB-powered.
  • Manual sample handling.
  • One measurement per sampling occasion.
  • LCD display for the operator’s reading.
  • Data integration requires manual entry or a separate SD card.

Inline process refractometers are designed for INTEGRATION into industrial process control systems:

  • Continuous 24/7/365 operation.
  • Automatic sample exposure — the liquid flows naturally over the measuring prism.
  • Reports the value continuously.
  • Signal output compatible with industry-standard control systems (4-20 mA, 0-10 V, HART, Profibus, Modbus).
  • No operator handling during normal operation.

IRIS belongs to the latter category — but with a unique design approach that sets it apart from traditional inline refractometers.

Smart sensor vs. dumb sensor: IRIS’s architectural innovation

Traditional inline refractometers follow a ”dumb sensor + control box” architecture:

  1. An OPTICAL SENSOR HEAD sits in the pipe. It contains an LED, prism, and photo detector.
  2. The sensor head is cable-connected to an EXTERNAL CONTROL BOX (typically a wall-mounted unit).
  3. The control box contains a microprocessor, LCD display, user buttons, and signal conversion electronics.
  4. The control box has an output to the control system via 4-20 mA or equivalent.

Drawbacks of this architecture:

  • The control box takes up wall space and requires its own power supply.
  • The cable between sensor and control box is vulnerable to mechanical damage.
  • Extra cost (control box typically 15,000-30,000 SEK).
  • Extra installation time for mounting and cable routing.
  • Extra maintenance point.

IRIS’s ”smart sensor” design eliminates the control box. The entire electronics module sits in the sensor head itself. Consequence: the unit connects DIRECTLY to the process control system via 4-20 mA or 0-10 V outputs. No intermediate link.

If the user needs a physical display, a cheap off-the-shelf meter for the 4-20 mA signal can be wired into the loop. But for modern plants where data is read on the operator’s HMI (Human Machine Interface) or SCADA system, no local display is necessary.

IRIS Inline process refractometer smart sensor for refractive index

4-20 mA signal: the industry standard

4-20 mA is the most widespread analog signal standard in industrial process control. Here’s how it works:

  • The instrument’s output is a CURRENT (not voltage) between 4 mA and 20 mA.
  • 4 mA represents the ”lowest possible measured value” (e.g. 0% Brix).
  • 20 mA represents the ”highest possible measured value” (e.g. 100% Brix).
  • Values in between are linearly interpolated. If IRIS measures 50% Brix, it sends 12 mA.

Why current instead of voltage? Three reasons:

  1. Cable-length independence: Current is constant throughout a circuit regardless of cable resistance. Voltage would drop over long cables. IRIS can sit 100+ meters from the control system without signal degradation.
  2. Electromagnetic noise tolerance: Current signals are less sensitive to electromagnetic interference from motors and transformers in industrial environments.
  3. Fault detection: A cable break gives 0 mA (not 4 mA). This is the signal ”fault — not a 0% value”. The control system can detect hardware faults directly.

All PLCs, DCS systems, and HMI panels in the industrial world have 4-20 mA inputs as standard.

Mounting flexibility

IRIS ships with a process adapter for mounting directly in the pipe flow. Standard variants:

  • Sanitary tri-clamp: Common in food, beverage, dairy, and pharmaceutical industries. Quick-connect, can be opened for CIP cleaning.
  • NPT or BSP thread: Standard industrial threads for smaller applications.
  • Flange connections (DIN, ANSI): For larger pipes and pressurized processes.
  • In-line tee mounting: For existing pipe installations where a cross tap-in is the simplest approach.

The measuring prism protrudes into the pipe stream’s internal diameter and is exposed directly to the liquid. The liquid flows over the prism continuously. No sampling, no human handling.

CIP compatibility (Cleaning-In-Place)

The food industry requires periodic cleaning of all process equipment. Typical CIP cycle:

  1. Alkaline solution (2-3% NaOH at 80°C) for 20-30 minutes.
  2. Rinse with clean water.
  3. Acid solution (1-2% HNO₃ at 60°C) for 15-20 minutes.
  4. Final rinse.
  5. Thermal sterilization (hot steam or water above 90°C).

IRIS is built to withstand this cycle without being disassembled. All liquid-contact surfaces are stainless steel (SS 316L) with food-grade seals (EPDM or FFKM depending on version). Always permanently mounted — it cannot fall, it cannot contaminate the process with external materials.

What IRIS measures — and what it ACTUALLY measures

The instrument measures refractive index (RI) directly. RI is the refraction index — the fundamental physical value, independent of liquid type. The key to interpreting RI as ”% Brix” or ”% dry substance” or ”% NaCl” is a CALIBRATION CURVE specific to the application.

IRIS comes with pre-loaded calibration curves for common applications:

  • Brix (sucrose solutions).
  • NaCl concentration.
  • Alcohol concentration.
  • Ethylene glycol/propylene glycol concentration.
  • Various chemicals (material-specific calibrations).

For custom applications, the operator can define their own calibration curve via 3-point calibration with known reference solutions. This makes IRIS adaptable to practically any flowing liquid with a clear RI-concentration relationship.

Applications

Fruit juice and concentrate production: Continuous Brix monitoring in evaporator loops. Modulates heat and pressure to keep target Brix stable.

Brewing: Wort Brix during the mashing process. Beer Brix during the fermentation phase. Automatic batch-to-batch consistency.

Dairy industry: Milk dry-substance measurement during concentration processes (milk powder production). Condensed milk Brix.

Sugar refining: Sugar solution Brix during the concentration and crystallization phase. Critical for yield optimization.

Preserve industry (agriculture): Fruit preserving, jam production, syrup concentration.

Chemical process: Concentration control of solutions (sulfuric acid, sodium hydroxide, nitric acid).

Pharmaceutical industry: Active-substance concentration in liquid formulation.

Water treatment: Salinity monitoring in seawater desalination plants. Membrane concentrate measurement.

Ethanol and biofuel production: Alcohol concentration during fermentation and distillation.

Coolant and chemical mixing plants: Automatic quality control of outgoing product.

CIP verification: During cleaning cycles, IRIS verifies that the cleaning solution has the correct concentration.

Lifespan and maintenance

  • The prism is sapphire glass for wear tolerance against the liquid flow. Lifespan typically 10+ years under normal operation.
  • The LED light source is of CIP-tolerant type. Lifespan 100,000+ hours.
  • The photo detector is solid-state, no mechanical parts that wear.
  • The electronics module is gel-filled for moisture tolerance during CIP cycles.
  • No calibration drift is expected during the first 5 years. After that, verification every 2-3 years.
  • In case of problems — no ”repair” — the module is replaced entirely.

What you get for your money

IRIS Inline process refractometer with intelligent smart-sensor architecture, direct 4-20 mA or 0-10 V output without external control box, refractive index measurement with pre-loaded calibration curves for Brix, NaCl, alcohol, glycol, chemicals, sapphire glass measuring prism, stainless steel SS 316L wetted surfaces, CIP-compatible without disassembly, sanitary tri-clamp connection standard (other flange or thread standards available), 24/7/365 continuous operation. 35,204 SEK.

The standard solution for industrial process integration of refractometer measurement. Handheld instruments work for basic QC and one-off measurements; inline instruments like IRIS are essential for automatic process control where continuous data is needed for control purposes. The price premium compared to handheld instruments (typically 30,000-40,000 SEK premium) is justified by labor savings (no manual sample handling), faster fault response (real-time vs. hour-long delay), and the ability to achieve fully automatic process control that eliminates operator error.

Read more: IRIS Inline process refractometer in the shop →